Assessment Year | 2016 |
---|---|
Principal Product | Plastic laminated wall systems and institutional furniture |
NAICS | 337127: Institutional Furniture Manufacturing |
SIC | 2542: Office and Store Fixtures, Partitions, Shelving, and Lockers, Except Wood |
Sales Range | $10 M to 50M |
# of Employees | 150 |
Plant Area |
160,000
ft2
|
Annual Production | 150,000
pieces
|
Production Hrs. Annual | 3,392
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $78,815 | 1,907,800 |
kWh
|
$0.041 |
Electricity Demand | $61,309 | 6,788 |
kW-mo/yr
|
$9.03 |
Electricity Fees | $5,209 | - |
|
- |
TOTAL YEARLY COSTS | $145,333 | |||
RECOMMENDED SAVINGS* | $32,760 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $32,510 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,350 | $1,000 |
$7,480
178,000
kWh
|
$4,870
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,680 | $41,400 |
$6,470
154,000
kWh
|
$4,210
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,110 | $6,410 |
$2,040
48,600
kWh
|
$1,070
-
kW-mo/yr
|
- | - | |
04 | 2.8121: Apply for tax-free status for energy purchases | $4,440 | $2,000 | - | - | $2,220 | $2,220 | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $840 | $10 |
$380
9,000
kWh
|
$460
-
kW-mo/yr
|
- | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $700 | $760 |
$700
16,640
kWh
|
- | - | - | |
07 | 2.7123: Keep lamps and reflectors clean | $390 | $57 |
$260
6,200
kWh
|
$130
-
kW-mo/yr
|
- | - | |
08 | 2.7124: Make a practice of turning off lights when not needed | $250 | - |
$250
5,990
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $32,760 | $51,637 |
$17,580
418,430
kWh
|
$10,740
-
kW-mo/yr
|
$2,220 | $2,220 | ||
TOTAL IMPLEMENTED | $32,510 | $51,637 |
$17,330
412,440
kWh
|
$10,740
-
kW-mo/yr
|
$2,220 | $2,220 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs