Assessment Year | 2016 |
---|---|
Principal Product | metal gratings |
NAICS | 332323: Ornamental and Architectural Metal Work Manufacturing |
SIC | 3446: Architectural and Ornamental Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
48,500
ft2
|
Annual Production | 56,000,000
lb
|
Production Hrs. Annual | 6,082
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $86,063 | 1,469,000 |
kWh
|
$0.059 |
Electricity Demand | $51,617 | 7,830 |
kW-mo/yr
|
$6.59 |
Electricity Fees | $1,114 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $23,430 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,282 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $10,300 | $23,900 | - |
$10,300
-
kW-mo/yr
|
- | |
02 | 2.8118: Check for accuracy of utility / power meters | $4,892 | - |
$4,892
-
kWh
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,503 | - |
$2,017
38,064
kWh
|
$486
-
kW-mo/yr
|
- | |
04 | 2.7124: Make a practice of turning off lights when not needed | $2,335 | $150 |
$1,750
33,035
kWh
|
$585
-
kW-mo/yr
|
- | |
05 | 2.4131: Size electric motors for peak operating efficiency | $1,035 | $13 |
$835
15,700
kWh
|
$200
-
kW-mo/yr
|
- | |
06 | 2.7145: Install skylights | $1,030 | $5,100 |
$1,030
19,415
kWh
|
- | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $440 | $19 |
$355
6,700
kWh
|
$85
-
kW-mo/yr
|
- | |
08 | 2.4322: Use or replace with energy efficient substitutes | $280 | $62 |
$120
2,290
kWh
|
$160
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $615 | $180 |
$195
3,680
kWh
|
$45
-
kW-mo/yr
|
$375 | |
TOTAL RECOMMENDED | $23,430 | $29,424 |
$11,194
118,884
kWh
|
$11,861
-
kW-mo/yr
|
$375 | ||
TOTAL IMPLEMENTED | $8,282 | $349 |
$7,192
43,415
kWh
|
$715
-
kW-mo/yr
|
$375 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs