Assessment Year | 2016 |
---|---|
Principal Product | plumbing fittings |
NAICS | 332913: Plumbing Fixture Fitting and Trim Manufacturing |
SIC | 3432: Plumbing Fixture Fittings and Trim |
Sales Range | $100 M to 500M |
# of Employees | 280 |
Plant Area |
163,000
ft2
|
Annual Production | 365,000,000
pieces
|
Production Hrs. Annual | 7,248
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $386,011 | 8,104,800 |
kWh
|
$0.048 |
Electricity Demand | $156,114 | 19,475 |
kW-mo/yr
|
$8.02 |
Electricity Fees | $11,843 | - |
|
- |
Natural Gas | $62,170 | 15,736 |
MMBtu
|
$3.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $71,469 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $54,900 | $270,000 |
$30,000
624,000
kWh
|
$24,900
-
kW-mo/yr
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,580 | $11 |
$5,060
106,200
kWh
|
$1,520
-
kW-mo/yr
|
- | |
03 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $4,142 | $63 |
$686
14,400
kWh
|
$2,780
-
kW-mo/yr
|
$676
-
MMBtu
|
|
04 | 2.3132: Recharge batteries on during off-peak demand periods | $2,700 | - | - |
$2,700
-
kW-mo/yr
|
- | |
05 | 2.4314: Use synthetic lubricant | $1,110 | - |
$760
15,968
kWh
|
$350
-
kW-mo/yr
|
- | |
06 | 2.2113: Repair or replace steam traps | $647 | $520 | - | - |
$647
-
MMBtu
|
|
07 | 2.4322: Use or replace with energy efficient substitutes | $630 | $1,450 |
$630
13,252
kWh
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $400 | $560 |
$313
6,590
kWh
|
$87
-
kW-mo/yr
|
- | |
09 | 2.7135: Install occupancy sensors | $360 | $460 |
$360
7,510
kWh
|
- | - | |
TOTAL RECOMMENDED | $71,469 | $273,064 |
$37,809
787,920
kWh
|
$32,337
-
kW-mo/yr
|
$1,323
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs