Assessment Year | 2015 |
---|---|
Principal Product | Bread and rolls |
NAICS | 311812: Commercial Bakeries |
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $50 M to 100M |
# of Employees | 180 |
Plant Area |
165,000
ft2
|
Annual Production | 94,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $450,740 | 10,435,451 |
kWh
|
$0.043 |
Electricity Demand | $218,809 | 20,350 |
kW-mo/yr
|
$10.75 |
Electricity Fees | $14,165 | - |
|
- |
Natural Gas | $329,829 | 66,318 |
MMBtu
|
$4.97 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,750 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $21,190 | $35,020 | - |
$21,190
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,345 | $2,000 |
$6,470
154,000
kWh
|
$2,875
-
kW-mo/yr
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,520 | $45 |
$4,900
116,840
kWh
|
$2,620
-
kW-mo/yr
|
- | |
04 | 2.4322: Use or replace with energy efficient substitutes | $1,450 | $3,100 |
$1,450
34,580
kWh
|
- | - | |
05 | 2.8123: Pay utility bills on time | $825 | - | - | - | $825 | |
06 | 2.7124: Make a practice of turning off lights when not needed | $210 | - |
$210
4,950
kWh
|
- | - | |
07 | 2.7135: Install occupancy sensors | $210 | $95 |
$210
5,040
kWh
|
- | - | |
TOTAL RECOMMENDED | $40,750 | $40,260 |
$13,240
315,410
kWh
|
$26,685
-
kW-mo/yr
|
$825 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs