Assessment Year | 2011 |
---|---|
Principal Product | Refurbished Blow-Out Preventers |
NAICS | 333132: Oil and Gas Field Machinery and Equipment Manufacturing |
SIC | 3533: Oil and Gas Field Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 61 |
Plant Area |
57,000
ft2
|
Annual Production | 800
pieces
|
Production Hrs. Annual | 7,440
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $117,110 | 2,015,763 |
kWh
|
$0.058 |
Electricity Demand | $47,134 | 7,958 |
kW-mo/yr
|
$5.92 |
Electricity Fees | $9,872 | - |
|
- |
Natural Gas | $52,346 | 5,395 |
MMBtu
|
$9.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $104,415 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $59,215 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 3.4151: Minimize water usage | $36,500 | $20,000 | - | - |
$(-2,170.0)
-
MMBtu
|
$38,670
-
Tgal
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $26,200 | $11,140 |
$21,000
357,000
kWh
|
$5,200
-
kW-mo/yr
|
- | - | - | |
03 | 3.5314: Use in-process recycling whenever possible | $17,240 | - | - | - | - | - | $17,240 | |
04 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $8,700 | - | - | - | - | - | $8,700 | |
05 | 2.3212: Optimize plant power factor | $6,100 | $14,200 | - |
$6,100
-
kW-mo/yr
|
- | - | - | |
06 | 2.7145: Install skylights | $5,600 | $100 |
$5,600
98,200
kWh
|
- | - | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,770 | $500 |
$3,010
52,000
kWh
|
$760
-
kW-mo/yr
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $195 | $600 |
$195
3,140
kWh
|
- | - | - | - | |
09 | 2.7124: Make a practice of turning off lights when not needed | $110 | - |
$110
1,900
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $104,415 | $46,540 |
$29,915
512,240
kWh
|
$12,060
-
kW-mo/yr
|
$(-2,170.0)
-
MMBtu
|
$38,670
-
Tgal
|
$25,940 | ||
TOTAL IMPLEMENTED | $59,215 | $26,540 |
$29,915
512,240
kWh
|
$12,060
-
kW-mo/yr
|
- | - | $17,240 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs