Assessment Year | 2010 |
---|---|
Principal Product | Carbonated soft drinks |
NAICS | 311930: Flavoring Syrup and Concentrate Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
320,000
ft2
|
Annual Production | 22,685,034
pieces
|
Production Hrs. Annual | 5,773
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $545,600 | 11,608,476 |
kWh
|
$0.047 |
Electricity Demand | $212,700 | 28,944 |
kW-mo/yr
|
$7.35 |
Natural Gas | $194,598 | 32,275 |
MMBtu
|
$6.03 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $48,437 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 3.4151: Minimize water usage | $24,800 | $10,000 | - | - | - | - | - |
$24,800
-
Tgal
|
|
02 | 2.1232: Keep boiler tubes clean | $7,100 | $5,000 | - | - | - |
$7,100
-
MMBtu
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,590 | $52,875 |
$5,900
128,160
kWh
|
$2,360
-
kW-mo/yr
|
- | - | $(-1,670.0) | - | |
04 | 2.4133: Use most efficient type of electric motors | $4,336 | $31,683 |
$3,097
67,335
kWh
|
$1,239
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.4314: Use synthetic lubricant | $1,845 | - |
$1,320
28,600
kWh
|
$525
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7124: Make a practice of turning off lights when not needed | $1,460 | - |
$960
20,800
kWh
|
$500
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,410 | $700 |
$1,000
22,100
kWh
|
$410
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.7124: Make a practice of turning off lights when not needed | $545 | - |
$545
11,860
kWh
|
- | - | - | - | - | |
09 | 2.2511: Insulate bare equipment | $240 | $185 | - | - | - |
$240
-
MMBtu
|
- | - | |
10 | 2.8118: Check for accuracy of utility / power meters | $111 | - | - | - | $111 | - | - | - | |
TOTAL RECOMMENDED | $48,437 | $100,443 |
$12,822
278,855
kWh
|
$5,034
-
kW-mo/yr
|
$111 |
$7,340
-
MMBtu
|
$(-1,670.0) |
$24,800
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs