Assessment Year | 2009 |
---|---|
Principal Product | Pork rinds and wheat based snack products |
NAICS | 311919: Other Snack Food Manufacturing |
SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
Sales Range | $10 M to 50M |
# of Employees | 65 |
Plant Area |
50,000
ft2
|
Annual Production | 9,000,000
lb
|
Production Hrs. Annual | 3,312
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $76,977 | 1,140,660 |
kWh
|
$0.067 |
Electricity Demand | $14,067 | 2,495 |
kW-mo/yr
|
$5.64 |
Electricity Fees | $7,755 | - |
|
- |
Natural Gas | $104,325 | 10,678 |
MMBtu
|
$9.77 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $10,044 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,934 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,800 | $14,966 |
$4,180
61,900
kWh
|
$1,240
-
kW-mo/yr
|
- | $380 | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,160 | $18 |
$1,700
25,110
kWh
|
$460
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,070 | $350 |
$810
12,000
kWh
|
$260
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $766 | $381 |
$160
2,400
kWh
|
$16
-
kW-mo/yr
|
$590 | - | |
05 | 2.7135: Install occupancy sensors | $138 | $100 |
$105
1,570
kWh
|
$33
-
kW-mo/yr
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $110 | $488 |
$85
1,242
kWh
|
$25
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $10,044 | $16,303 |
$7,040
104,222
kWh
|
$2,034
-
kW-mo/yr
|
$590 | $380 | ||
TOTAL IMPLEMENTED | $9,934 | $15,815 |
$6,955
102,980
kWh
|
$2,009
-
kW-mo/yr
|
$590 | $380 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs