Assessment Year | 2007 |
---|---|
Principal Product | Snack foods |
NAICS | 311919: Other Snack Food Manufacturing |
SIC | 2096: Potato Chips, Corn Chips, and Similar Snacks |
Sales Range | $100 M to 500M |
# of Employees | 285 |
Plant Area |
157,000
ft2
|
Annual Production | 75,000,000
lb
|
Production Hrs. Annual | 8,640
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $537,836 | 13,894,560 |
kWh
|
$0.039 |
Electricity Demand | $171,567 | 25,655 |
kW-mo/yr
|
$6.69 |
Electricity Fees | $44,421 | - |
|
- |
Natural Gas | $1,937,301 | 208,095 |
MMBtu
|
$9.31 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $15,290 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,590 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|
01 | 3.4114: Replace city water with recycled water via cooling tower | $9,500 | $6,500 | - | - |
$9,500
-
Tgal
|
|
02 | 2.4239: Eliminate or reduce compressed air usage | $3,100 | - |
$2,400
51,000
kWh
|
$700
-
kW-mo/yr
|
- | |
03 | 2.7229: Air condition only space necessary | $1,700 | $5,200 |
$1,300
27,000
kWh
|
$400
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $670 | $285 |
$500
10,600
kWh
|
$170
-
kW-mo/yr
|
- | |
05 | 2.7131: Add area lighting switches | $320 | $65 |
$320
6,800
kWh
|
- | - | |
TOTAL RECOMMENDED | $15,290 | $12,050 |
$4,520
95,400
kWh
|
$1,270
-
kW-mo/yr
|
$9,500
-
Tgal
|
||
TOTAL IMPLEMENTED | $13,590 | $6,850 |
$3,220
68,400
kWh
|
$870
-
kW-mo/yr
|
$9,500
-
Tgal
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs