Assessment Year | 2006 |
---|---|
Principal Product | Bottled water and juice |
NAICS | 312112: Bottled Water Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $5 M to 10M |
# of Employees | 30 |
Plant Area |
33,000
ft2
|
Annual Production | 600
Tgal
|
Production Hrs. Annual | 1,990
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $43,994 | 531,734 |
kWh
|
$0.083 |
Electricity Demand | $9,153 | 2,900 |
kW-mo/yr
|
$3.16 |
Natural Gas | $7,475 | 777 |
MMBtu
|
$9.62 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,749 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2121: Increase amount of condensate returned | $8,400 | $2,190 | - | - | - |
$6,600
-
MMBtu
|
- |
$1,800
-
Tgal
|
|
02 | 4.454: Modify startup/shutdown times | $7,024 | - | - | - | $7,024 | - | - | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,950 | $500 |
$2,410
28,060
kWh
|
$540
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.6218: Turn off equipment when not in use | $2,700 | $270 |
$2,700
31,600
kWh
|
- | - | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $295 | $140 |
$170
1,970
kWh
|
$37
-
kW-mo/yr
|
- | - | $88 | - | |
06 | 2.7124: Make a practice of turning off lights when not needed | $210 | $50 |
$190
2,170
kWh
|
$20
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $190 | - |
$190
2,200
kWh
|
- | - | - | - | - | |
08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,980 | $500 | - | - | - |
$3,980
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $25,749 | $3,650 |
$5,660
66,000
kWh
|
$597
-
kW-mo/yr
|
$7,024 |
$10,580
-
MMBtu
|
$88 |
$1,800
-
Tgal
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Personnel Changes Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs