Assessment Year | 2005 |
---|---|
Principal Product | Newspaper inserts, mailings |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
Sales Range | $50 M to 100M |
# of Employees | 154 |
Plant Area |
132,000
ft2
|
Annual Production | 9,280,000
pieces
|
Production Hrs. Annual | 4,732
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $318,522 | 5,977,488 |
kWh
|
$0.053 |
Electricity Demand | $66,920 | 15,334 |
kW-mo/yr
|
$4.36 |
Electricity Fees | $9,816 | - |
|
- |
Natural Gas | $5,527 | 525 |
MMBtu
|
$10.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $67,600 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $54,620 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $45,000 | $1,000 |
$34,600
653,000
kWh
|
$10,400
-
kW-mo/yr
|
- | |
02 | 2.7124: Make a practice of turning off lights when not needed | $4,560 | - |
$3,400
64,100
kWh
|
$1,160
-
kW-mo/yr
|
- | |
03 | 2.6218: Turn off equipment when not in use | $3,030 | - |
$3,030
57,200
kWh
|
- | - | |
04 | 2.7124: Make a practice of turning off lights when not needed | $2,600 | - |
$2,600
49,140
kWh
|
- | - | |
05 | 3.7123: Use continuous processing | $2,500 | - | - | - | $2,500 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,390 | $1,270 |
$430
8,100
kWh
|
$60
-
kW-mo/yr
|
$1,900 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,000 | - |
$1,560
29,400
kWh
|
$440
-
kW-mo/yr
|
- | |
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,690 | $4 |
$1,300
24,500
kWh
|
$390
-
kW-mo/yr
|
- | |
09 | 2.6218: Turn off equipment when not in use | $1,560 | - |
$1,560
29,500
kWh
|
- | - | |
10 | 2.7124: Make a practice of turning off lights when not needed | $950 | $150 |
$730
13,800
kWh
|
$220
-
kW-mo/yr
|
- | |
11 | 2.4314: Use synthetic lubricant | $690 | - |
$430
8,100
kWh
|
$260
-
kW-mo/yr
|
- | |
12 | 2.7124: Make a practice of turning off lights when not needed | $630 | - |
$500
9,400
kWh
|
$130
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $67,600 | $2,424 |
$50,140
946,240
kWh
|
$13,060
-
kW-mo/yr
|
$4,400 | ||
TOTAL IMPLEMENTED | $54,620 | $2,424 |
$41,650
786,100
kWh
|
$11,070
-
kW-mo/yr
|
$1,900 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs