Assessment Year | 2005 |
---|---|
Principal Product | Flotation devices |
NAICS | 326140: Polystyrene Foam Product Manufacturing |
SIC | 3535: Conveyors and Conveying Equipment |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
58,678
ft2
|
Annual Production | 11,520
pieces
|
Production Hrs. Annual | 8,496
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $187,812 | 2,637,892 |
kWh
|
$0.071 |
Electricity Demand | $37,540 | 9,432 |
kW-mo/yr
|
$3.98 |
Electricity Fees | $1,500 | - |
|
- |
Natural Gas | $69,267 | 6,622 |
MMBtu
|
$10.46 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $60,575 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $58,505 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $33,171 | $10,165 | - | - | - | $12,840 | $20,331 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,020 | $500 |
$9,970
160,830
kWh
|
$1,050
-
kW-mo/yr
|
- | - | - | |
03 | 2.3212: Optimize plant power factor | $7,410 | $19,235 | - |
$7,410
-
kW-mo/yr
|
- | - | - | |
04 | 2.4133: Use most efficient type of electric motors | $1,310 | $8,146 |
$1,310
21,166
kWh
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,160 | - |
$1,930
31,090
kWh
|
$230
-
kW-mo/yr
|
- | - | - | |
06 | 2.7145: Install skylights | $1,700 | - |
$1,700
24,500
kWh
|
- | - | - | - | |
07 | 2.7124: Make a practice of turning off lights when not needed | $1,650 | - |
$1,300
20,940
kWh
|
$350
-
kW-mo/yr
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $744 | $500 |
$270
4,330
kWh
|
$24
-
kW-mo/yr
|
$450 | - | - | |
09 | 2.7124: Make a practice of turning off lights when not needed | $760 | - |
$650
10,500
kWh
|
$110
-
kW-mo/yr
|
- | - | - | |
10 | 2.4314: Use synthetic lubricant | $440 | - |
$380
5,500
kWh
|
$60
-
kW-mo/yr
|
- | - | - | |
11 | 2.7134: Use photocell controls | $210 | - |
$210
3,365
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $60,575 | $38,546 |
$17,720
282,221
kWh
|
$9,234
-
kW-mo/yr
|
$450 | $12,840 | $20,331 | ||
TOTAL IMPLEMENTED | $58,505 | $30,400 |
$15,760
250,555
kWh
|
$9,124
-
kW-mo/yr
|
$450 | $12,840 | $20,331 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs