| Assessment Year | 2004 |
|---|---|
| Principal Product | Industrial and agricultural mowing equipment |
| NAICS | 333112: Lawn and Garden Tractor and Home Lawn and Garden Equipment Manufacturing |
| SIC | 3524: Lawn and Garden Tractors and Home Lawn and Garden Equipment |
| Sales Range | $50 M to 100M |
| # of Employees | 150 |
| Plant Area |
275,000
ft2
|
| Annual Production | 2,640
pieces
|
| Production Hrs. Annual | 2,228
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $132,340 | 2,471,665 |
kWh
|
$0.054 |
| Electricity Fees | $6,000 | - |
|
- |
| Natural Gas | $64,338 | 8,420 |
MMBtu
|
$7.64 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $147,978 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $1,528 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 3.2123: Convert to high volume low pressure (hvlp) paint guns | $141,300 | $680 | - | - |
$44,200
-
lb
|
- | $97,100 | |
| 02 | 3.7132: Reuse rags until completely soiled | $1,800 | - | - | - | - | - | $1,800 | |
| 03 | 2.2414: Use waste heat from hot flue gases to preheat | $3,350 | $14,400 | - |
$3,350
-
MMBtu
|
- | - | - | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $680 | $1,500 |
$680
12,500
kWh
|
- | - | - | - | |
| 05 | 2.8112: Combine utility meters | $528 | - | - | - | - | $528 | - | |
| 06 | 2.6218: Turn off equipment when not in use | $200 | - |
$200
3,700
kWh
|
- | - | - | - | |
| 07 | 2.7124: Make a practice of turning off lights when not needed | $120 | $74 |
$120
2,270
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $147,978 | $16,654 |
$1,000
18,470
kWh
|
$3,350
-
MMBtu
|
$44,200
-
lb
|
$528 | $98,900 | ||
| TOTAL IMPLEMENTED | $1,528 | $1,574 |
$1,000
18,470
kWh
|
- | - | $528 | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs