Assessment Year | 2003 |
---|---|
Principal Product | Junction boxes and aluminum enclosures |
NAICS | 332322: Sheet Metal Work Manufacturing |
SIC | 3644: Noncurrent-Carrying Wiring Devices |
Sales Range | $10 M to 50M |
# of Employees | 140 |
Plant Area |
84,000
ft2
|
Annual Production | 624
ton
|
Production Hrs. Annual | 4,625
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $152,868 | 2,159,557 |
kWh
|
$0.071 |
Electricity Demand | $24,945 | 8,962 |
kW-mo/yr
|
$2.78 |
Electricity Fees | $425 | - |
|
- |
Natural Gas | $105,601 | 14,195 |
MMBtu
|
$7.44 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,065 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $8,980 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $13,040 | $12,960 | - |
$13,040
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,160 | $500 |
$5,160
81,500
kWh
|
- | - | - | - | |
03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $3,300 | $15,770 | n/a |
$3,300
69,800
kWh
|
- | - | - | - |
04 | 2.7141: Lower light fixtures in high ceiling areas | $1,830 | - |
$1,100
17,400
kWh
|
$730
-
kW-mo/yr
|
- | - | - | |
05 | 3.7132: Reuse rags until completely soiled | $1,790 | $1,910 | - | - | - | - | $1,790 | |
06 | 2.2514: Cover open tanks | $940 | $500 | - | - |
$940
-
MMBtu
|
- | - | |
07 | 2.2514: Cover open tanks | $805 | $500 | - | - |
$805
-
MMBtu
|
- | - | |
08 | 4.821: Pay bills on time to avoid late fees | $200 | - | - | - | - | $200 | - | |
TOTAL RECOMMENDED | $27,065 | $32,140 |
$9,560
168,700
kWh
|
$13,770
-
kW-mo/yr
|
$1,745
-
MMBtu
|
$200 | $1,790 | ||
TOTAL IMPLEMENTED | $8,980 | $2,410 |
$6,260
98,900
kWh
|
$730
-
kW-mo/yr
|
- | $200 | $1,790 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs