Assessment Year 2003
Principal Product Batteries and power conversion devices
NAICS 335911: Storage Battery Manufacturing
SIC 3691: Storage Batteries
Sales Range $10
M
to 50
M
# of Employees 170
Plant Area 50,000
ft2
Annual Production 10,000
pieces
Production Hrs. Annual 1,992
hrs
Location (State) Texas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $334,800 7,596,617
kWh
Electricity Demand $85,503 23,532
kW-mo/yr
Electricity Fees $(-3,863.0) -
Natural Gas $56,117 9,448
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $27,210 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $16,940

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Other Liquid (haz) Savings Personnel Changes Savings Ancillary Material Cost Savings One-time Revenue or Avoided Cost Savings
01 4.652: Replace existing equipment with more suitable substitutes $10,000 $40,000 - - - $10,000 - -
02 3.1191: Change procedures / equipment / operating conditions $7,310 - - - - - $7,310 -
03 2.3131: Reschedule plant operations or reduce load to avoid peaks $4,850 - - $4,850
-
kW-mo/yr
- - - -
04 2.4231: Reduce the pressure of compressed air to the minimum required $2,060 - $1,540
34,200
kWh
$520
-
kW-mo/yr
- - - -
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,060 $500 $1,060
23,570
kWh
- - - - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $760 $650 $190
4,170
kWh
- - $570 - -
07 4.132: Purchase new equipment to reduce material use / cost $730 $250 - - $100
-
gal
- $630 -
08 2.8118: Check for accuracy of utility / power meters $300 - - - - - - $300
09 2.7134: Use photocell controls $140 $65 $113
2,520
kWh
$27
-
kW-mo/yr
- - - -
TOTAL RECOMMENDED $27,210 $41,465 $2,903
64,460
kWh
$5,397
-
kW-mo/yr
$100
-
gal
$10,570 $7,940 $300
TOTAL IMPLEMENTED $16,940 $40,750 $1,060
23,570
kWh
$4,850
-
kW-mo/yr
$100
-
gal
$10,000 $630 $300
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Other Liquid (haz) Savings Personnel Changes Savings Ancillary Material Cost Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs