Assessment Year | 2003 |
---|---|
Principal Product | Life science products |
NAICS | 325414: Biological Product (except Diagnostic) Manufacturing |
SIC | 2836: Biological Products, Except Diagnostic Substances |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
80,000
ft2
|
Annual Production | 10,800
pieces
|
Production Hrs. Annual | 3,024
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $125,634 | 2,686,308 |
kWh
|
$0.047 |
Electricity Demand | $41,359 | 5,515 |
kW-mo/yr
|
$7.50 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $41,760 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $34,230 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $23,400 | $240 |
$23,400
545,000
kWh
|
- | - | - | - | |
02 | 2.3212: Optimize plant power factor | $5,030 | $11,900 | - |
$5,030
-
kW-mo/yr
|
- | - | - | |
03 | 2.2622: Replace existing chiller with high efficiency model | $3,480 | $5,640 |
$2,080
48,360
kWh
|
- | - | $1,400 | - | |
04 | 3.6192: Use a less expensive method of waste removal | $2,100 | - | - | - |
$2,100
-
lb
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,460 | $1,790 |
$240
5,550
kWh
|
$150
-
kW-mo/yr
|
- | $1,070 | - | |
06 | 2.7423: Reduce heat gain by window tinting | $1,720 | $4,460 |
$1,720
40,000
kWh
|
- | - | - | - | |
07 | 4.821: Pay bills on time to avoid late fees | $750 | - | - | - | - | - | $750 | |
08 | 2.6218: Turn off equipment when not in use | $1,150 | - |
$680
15,400
kWh
|
$470
-
kW-mo/yr
|
- | - | - | |
09 | 2.6218: Turn off equipment when not in use | $1,130 | - |
$1,130
26,440
kWh
|
- | - | - | - | |
10 | 2.7111: Reduce illumination to minimum necessary levels | $780 | $1,520 |
$460
10,700
kWh
|
$320
-
kW-mo/yr
|
- | - | - | |
11 | 2.7124: Make a practice of turning off lights when not needed | $760 | - |
$760
17,800
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $41,760 | $25,550 |
$30,470
709,250
kWh
|
$5,970
-
kW-mo/yr
|
$2,100
-
lb
|
$2,470 | $750 | ||
TOTAL IMPLEMENTED | $34,230 | $7,670 |
$28,290
658,550
kWh
|
$620
-
kW-mo/yr
|
$2,100
-
lb
|
$2,470 | $750 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs