Assessment Year | 2001 |
---|---|
Principal Product | Oil & Water Well Screens |
NAICS |
n/a
|
SIC | 3533: Oil and Gas Field Machinery and Equipment |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
70,000
ft2
|
Annual Production | 262
thousand feet
|
Production Hrs. Annual | 0
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $95,040 | 1,529,050 |
kWh
|
$0.062 |
Electricity Demand | $15,973 | 5,512 |
kW-mo/yr
|
$2.90 |
Natural Gas | $29,800 | 5,166 |
MMBtu
|
$5.77 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $46,145 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,625 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $15,625 | $1,250 |
$15,625
258,300
kWh
|
- | - | - | - | |
02 | 2.3212: Optimize plant power factor | $4,760 | $4,500 | - |
$4,760
-
kW-mo/yr
|
- | - | - | |
03 | 3.3131: Use evaporation to concentrate material | $4,480 | $7,000 | - | - | - |
$4,480
-
Tgal
|
- | |
04 | 2.7145: Install skylights | $3,400 | $9,860 |
$3,400
67,700
kWh
|
- | - | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $3,340 | $5,705 |
$2,610
40,685
kWh
|
$730
-
kW-mo/yr
|
- | - | - | |
06 | 2.3212: Optimize plant power factor | $2,450 | $4,330 | - |
$2,450
-
kW-mo/yr
|
- | - | - | |
07 | 2.6218: Turn off equipment when not in use | $2,300 | - |
$2,300
32,300
kWh
|
- | - | - | - | |
08 | 2.7124: Make a practice of turning off lights when not needed | $2,280 | - |
$2,280
32,060
kWh
|
- | - | - | - | |
09 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $1,640 | $240 | - | - |
$1,640
-
MMBtu
|
- | - | |
10 | 2.6218: Turn off equipment when not in use | $1,250 | - | - | - |
$1,250
-
MMBtu
|
- | - | |
11 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,220 | $2,000 |
$1,070
15,000
kWh
|
$150
-
kW-mo/yr
|
- | - | - | |
12 | 2.7145: Install skylights | $1,000 | $3,170 |
$1,000
14,100
kWh
|
- | - | - | - | |
13 | 4.821: Pay bills on time to avoid late fees | $975 | - | - | - | - | - | $975 | |
14 | 2.4314: Use synthetic lubricant | $655 | - |
$530
7,880
kWh
|
$125
-
kW-mo/yr
|
- | - | - | |
15 | 2.3212: Optimize plant power factor | $395 | $1,875 | - |
$395
-
kW-mo/yr
|
- | - | - | |
16 | 2.7134: Use photocell controls | $375 | - |
$260
3,360
kWh
|
$115
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $46,145 | $39,930 |
$29,075
471,385
kWh
|
$8,725
-
kW-mo/yr
|
$2,890
-
MMBtu
|
$4,480
-
Tgal
|
$975 | ||
TOTAL IMPLEMENTED | $30,625 | $13,955 |
$23,075
366,705
kWh
|
$845
-
kW-mo/yr
|
$1,250
-
MMBtu
|
$4,480
-
Tgal
|
$975 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs