Assessment Year | 2000 |
---|---|
Principal Product | Cabinets |
NAICS |
n/a
|
SIC | 2434: Wood Kitchen Cabinets |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
150,000
ft2
|
Annual Production | 267,028
pieces
|
Production Hrs. Annual | 2,325
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $88,150 | 1,410,023 |
kWh
|
$0.063 |
Electricity Demand | $18,002 | 5,927 |
kW-mo/yr
|
$3.04 |
Electricity Fees | $812 | - |
|
- |
Natural Gas | $23,674 | 6,423 |
MMBtu
|
$3.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $133,721 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,021 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 3.5311: Recover and reuse waste material | $60,700 | - | - | - |
$60,700
-
lb
|
- | - | |
02 | 4.114: Add/modify equipment to improve drying process | $51,000 | $780 | - | - | - | - | $51,000 | |
03 | 2.4239: Eliminate or reduce compressed air usage | $10,000 | $2,240 |
$10,000
196,366
kWh
|
- | - | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,370 | $2,000 |
$7,370
141,559
kWh
|
- | - | - | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,280 | $500 |
$1,280
24,912
kWh
|
- | - | - | - | |
06 | 2.3212: Optimize plant power factor | $2,620 | $8,100 | - |
$2,620
-
kW-mo/yr
|
- | - | - | |
07 | 4.821: Pay bills on time to avoid late fees | $581 | - | - | - | - | $581 | - | |
08 | 2.7124: Make a practice of turning off lights when not needed | $170 | $140 |
$170
3,517
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $133,721 | $13,760 |
$18,820
366,354
kWh
|
$2,620
-
kW-mo/yr
|
$60,700
-
lb
|
$581 | $51,000 | ||
TOTAL IMPLEMENTED | $22,021 | $12,980 |
$18,820
366,354
kWh
|
$2,620
-
kW-mo/yr
|
- | $581 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs