Assessment Year | 1997 |
---|---|
Principal Product | Valves and abrasion resistant steel plates |
NAICS |
n/a
|
SIC | 3491: Industrial Valves |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
113,900
ft2
|
Annual Production | 3,000
pieces
|
Production Hrs. Annual | 4,576
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $233,974 | 6,163,834 |
kWh
|
$0.038 |
Electricity Demand | $87,537 | 14,674 |
kW-mo/yr
|
$5.97 |
Electricity Fees | $6,340 | - |
|
- |
Natural Gas | $61,485 | 11,423 |
MMBtu
|
$5.38 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $86,105 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $73,110 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.611: Begin a practice of predictive / preventative maintenance | $39,645 | $4,200 |
$1,895
77,960
kWh
|
- | - | - | $37,750 | |
02 | 3.6192: Use a less expensive method of waste removal | $6,870 | - | - | - |
$6,870
-
gal
|
- | - | |
03 | 3.7198: Reduce / eliminate use of disposable product | $5,675 | $150 | - | - | - |
$5,675
-
lb
|
- | |
04 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $6,115 | - | - | - | - |
$6,115
-
lb
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,790 | $675 |
$2,790
114,889
kWh
|
- | - | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,505 | $50 |
$715
22,567
kWh
|
$790
-
kW-mo/yr
|
- | - | - | |
07 | 2.4314: Use synthetic lubricant | $1,205 | - |
$555
22,860
kWh
|
$650
-
kW-mo/yr
|
- | - | - | |
08 | 2.4133: Use most efficient type of electric motors | $850 | $1,960 |
$460
19,050
kWh
|
$390
-
kW-mo/yr
|
- | - | - | |
09 | 2.7124: Make a practice of turning off lights when not needed | $785 | $150 |
$280
11,430
kWh
|
$505
-
kW-mo/yr
|
- | - | - | |
10 | 2.7145: Install skylights | $20,665 | $9,300 |
$20,665
84,994
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $86,105 | $16,485 |
$27,360
353,750
kWh
|
$2,335
-
kW-mo/yr
|
$6,870
-
gal
|
$11,790
-
lb
|
$37,750 | ||
TOTAL IMPLEMENTED | $73,110 | $16,335 |
$26,805
330,890
kWh
|
$1,685
-
kW-mo/yr
|
$6,870
-
gal
|
- | $37,750 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs