Assessment Year | 1997 |
---|---|
Principal Product | Barges, repaired & built |
NAICS |
n/a
|
SIC | 3731: Ship Building and Repairing |
Sales Range | $10 M to 50M |
# of Employees | 260 |
Plant Area |
n/a
|
Annual Production | 1,750
pieces
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $267,948 | 7,868,699 |
kWh
|
$0.034 |
Electricity Demand | $107,635 | 17,316 |
kW-mo/yr
|
$6.22 |
Electricity Fees | $27,541 | - |
|
- |
Natural Gas | $161,402 | 46,342 |
MMBtu
|
$3.48 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $16,750 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,000 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2136: Install / repair insulation on steam lines | $4,660 | $920 | - | - |
$4,660
-
MMBtu
|
|
02 | 2.1233: Analyze flue gas for proper air/fuel ratio | $3,310 | $500 | - | - |
$3,310
-
MMBtu
|
|
03 | 2.3134: Shift from daytime to nighttime operation | $3,100 | - | - |
$3,100
-
kW-mo/yr
|
- | |
04 | 2.4314: Use synthetic lubricant | $2,130 | - |
$1,120
50,996
kWh
|
$1,010
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,500 | $300 | - | - |
$1,500
-
MMBtu
|
|
06 | 2.7124: Make a practice of turning off lights when not needed | $1,300 | $150 |
$440
19,930
kWh
|
$860
-
kW-mo/yr
|
- | |
07 | 2.6212: Turn off equipment during breaks, reduce operating time | $750 | - |
$750
34,291
kWh
|
- | - | |
TOTAL RECOMMENDED | $16,750 | $1,870 |
$2,310
105,217
kWh
|
$4,970
-
kW-mo/yr
|
$9,470
-
MMBtu
|
||
TOTAL IMPLEMENTED | $16,000 | $1,870 |
$1,560
70,926
kWh
|
$4,970
-
kW-mo/yr
|
$9,470
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs