| Assessment Year | 1997 |
|---|---|
| Principal Product | Polyethylene sheeting |
| NAICS |
n/a
|
| SIC | 3081: Unsupported Plastics Film and Sheet |
| Sales Range | $50 M to 100M |
| # of Employees | 50 |
| Plant Area |
75,000
ft2
|
| Annual Production | 60,000,000
lb
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $456,387 | 15,339,391 |
kWh
|
$0.030 |
| Electricity Demand | $195,826 | 29,314 |
kW-mo/yr
|
$6.68 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $172,995 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $163,390 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.3212: Optimize plant power factor | $98,400 | $167,600 | - |
$98,400
-
kW-mo/yr
|
- | |
| 02 | 3.1191: Change procedures / equipment / operating conditions | $24,880 | $1,000 | - | - |
$24,880
-
lb
|
|
| 03 | 3.1192: Reduce scrap production | $23,650 | $6,000 | - | - |
$23,650
-
lb
|
|
| 04 | 3.5313: Increase amount of waste recovered for resale | $13,260 | - | - | - |
$13,260
-
lb
|
|
| 05 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $4,105 | - |
$745
33,705
kWh
|
$3,360
-
kW-mo/yr
|
- | |
| 06 | 2.7145: Install skylights | $2,080 | $6,930 |
$2,080
94,373
kWh
|
- | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,820 | $1,790 |
$1,000
45,428
kWh
|
$820
-
kW-mo/yr
|
- | |
| 08 | 2.4314: Use synthetic lubricant | $1,600 | - |
$830
37,515
kWh
|
$770
-
kW-mo/yr
|
- | |
| 09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,450 | $40 |
$760
34,584
kWh
|
$690
-
kW-mo/yr
|
- | |
| 10 | 2.7111: Reduce illumination to minimum necessary levels | $800 | - |
$270
12,309
kWh
|
$530
-
kW-mo/yr
|
- | |
| 11 | 2.2511: Insulate bare equipment | $750 | $230 |
$410
18,464
kWh
|
$340
-
kW-mo/yr
|
- | |
| 12 | 2.7124: Make a practice of turning off lights when not needed | $200 | $214 |
$200
9,086
kWh
|
- | - | |
| TOTAL RECOMMENDED | $172,995 | $183,804 |
$6,295
285,464
kWh
|
$104,910
-
kW-mo/yr
|
$61,790
-
lb
|
||
| TOTAL IMPLEMENTED | $163,390 | $175,084 |
$1,640
74,443
kWh
|
$99,960
-
kW-mo/yr
|
$61,790
-
lb
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs