Assessment Year | 1996 |
---|---|
Principal Product | Soft drinks |
NAICS |
n/a
|
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $50 M to 100M |
# of Employees | 95 |
Plant Area |
140,000
ft2
|
Annual Production | 77,175,000
Tgal
|
Production Hrs. Annual | 4,640
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $302,974 | 6,981,829 |
kWh
|
$0.043 |
Electricity Demand | $145,375 | 21,316 |
kW-mo/yr
|
$6.82 |
Electricity Fees | $7,719 | - |
|
- |
Natural Gas | $207,125 | 38,152 |
MMBtu
|
$5.43 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $59,598 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,061 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Other Liquid (haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.1331: Burn a less expensive grade of fuel | $40,374 | $40,400 | - | - |
$207,059
-
MMBtu
|
$(-166,685.0)
-
MMBtu
|
- | |
02 | 2.3212: Optimize plant power factor | $9,900 | $25,000 | - |
$9,900
-
kW-mo/yr
|
- | - | - | |
03 | 2.4239: Eliminate or reduce compressed air usage | $4,000 | $1,300 |
$4,000
129,543
kWh
|
- | - | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,100 | $1,000 |
$2,100
68,581
kWh
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $960 | $1,020 |
$530
16,999
kWh
|
$430
-
kW-mo/yr
|
- | - | - | |
06 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $970 | $810 |
$970
31,360
kWh
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $617 | $260 |
$254
8,206
kWh
|
$363
-
kW-mo/yr
|
- | - | - | |
08 | 3.1161: Eliminate/reduce an operation | $677 | $1,030 | - | - | - | - |
$677
-
gal
|
|
TOTAL RECOMMENDED | $59,598 | $70,820 |
$7,854
254,689
kWh
|
$10,693
-
kW-mo/yr
|
$207,059
-
MMBtu
|
$(-166,685.0)
-
MMBtu
|
$677
-
gal
|
||
TOTAL IMPLEMENTED | $48,061 | $43,770 |
$7,324
237,690
kWh
|
$363
-
kW-mo/yr
|
$207,059
-
MMBtu
|
$(-166,685.0)
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings | Other Liquid (haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs