| Assessment Year | 1996 |
|---|---|
| Principal Product | Thread and line pipe protectors |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 89 |
| Plant Area |
36,600
ft2
|
| Annual Production | 3,100,000
pieces
|
| Production Hrs. Annual | 8,496
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $142,342 | 2,696,366 |
kWh
|
$0.053 |
| Electricity Demand | $22,375 | 6,701 |
kW-mo/yr
|
$3.34 |
| Electricity Fees | $1,197 | - |
|
- |
| Natural Gas | $8,414 | 1,574 |
MMBtu
|
$5.35 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $16,780 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $11,395 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.8114: Change rate schedules or other changes in utility service | $5,385 | - | - |
$(-21,080.0)
-
kW-mo/yr
|
$(-5,650.0) | - | $32,115 | |
| 02 | 2.4133: Use most efficient type of electric motors | $1,685 | $765 |
$869
37,808
kWh
|
$816
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.3134: Shift from daytime to nighttime operation | $1,690 | - | - |
$1,690
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.2511: Insulate bare equipment | $1,150 | $600 |
$1,150
49,824
kWh
|
- | - | - | - | |
| 05 | 2.4314: Use synthetic lubricant | $440 | - |
$180
7,913
kWh
|
$260
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $400 | $296 |
$80
3,517
kWh
|
$320
-
kW-mo/yr
|
- | - | - | |
| 07 | 3.5212: Regrind, reuse, or sell scrap plastic parts | $5,490 | $10,000 | - | - | - |
$5,490
-
lb
|
- | |
| 08 | 3.7198: Reduce / eliminate use of disposable product | $540 | $110 | - | - | - |
$540
-
lb
|
- | |
| TOTAL RECOMMENDED | $16,780 | $11,771 |
$2,279
99,062
kWh
|
$(-17,994.0)
-
kW-mo/yr
|
$(-5,650.0) |
$6,030
-
lb
|
$32,115 | ||
| TOTAL IMPLEMENTED | $11,395 | $11,771 |
$2,279
99,062
kWh
|
$3,086
-
kW-mo/yr
|
- |
$6,030
-
lb
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs