Assessment Year | 1995 |
---|---|
Principal Product | Plywood |
NAICS |
n/a
|
SIC | 2436: Softwood Veneer and Plywood |
Sales Range | $50 M to 100M |
# of Employees | 350 |
Plant Area |
260,000
ft2
|
Annual Production | 262
thousand feet
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,883,776 | 40,215,417 |
kWh
|
$0.047 |
Wood | $340,000 | 595,000 |
MMBtu
|
$0.57 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $93,620 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $93,620 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Wood Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $43,500 | $2,000 |
$43,500
905,627
kWh
|
- | |
02 | 2.4314: Use synthetic lubricant | $12,500 | - |
$12,500
259,965
kWh
|
- | |
03 | 2.7145: Install skylights | $10,500 | $2,380 |
$10,500
218,933
kWh
|
- | |
04 | 2.2135: Repair and eliminate steam leaks | $9,990 | - | - |
$9,990
-
MMBtu
|
|
05 | 2.4133: Use most efficient type of electric motors | $7,410 | $7,260 |
$7,410
154,455
kWh
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,260 | $60 |
$7,260
150,938
kWh
|
- | |
07 | 2.7134: Use photocell controls | $1,500 | $305 |
$1,500
31,360
kWh
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $960 | $224 |
$960
19,930
kWh
|
- | |
TOTAL RECOMMENDED | $93,620 | $12,229 |
$83,630
1,741,208
kWh
|
$9,990
-
MMBtu
|
||
TOTAL IMPLEMENTED | $93,620 | $12,229 |
$83,630
1,741,208
kWh
|
$9,990
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Wood Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs