Assessment Year | 1994 |
---|---|
Principal Product | Printed heavy-duty plastic film shipping sacks |
NAICS |
n/a
|
SIC | 2671: Packaging Paper and Plastics Film, Coated and Laminated |
Sales Range | $10 M to 50M |
# of Employees | 250 |
Plant Area |
n/a
|
Annual Production | 32,000,000
lb
|
Production Hrs. Annual | 8,688
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $909,834 | 20,723,330 |
kWh
|
$0.044 |
Natural Gas | $121,529 | 37,389 |
MMBtu
|
$3.25 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $77,432 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $47,882 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $33,400 | - |
$33,400
726,846
kWh
|
|
02 | 2.3511: Use plant owned transformers or lease transformers | $14,100 | $19,783 |
$14,100
(-145,076)
kWh
|
|
03 | 2.2691: Shut off cooling if cold outside air will cool process | $22,270 | $51,520 |
$22,270
614,302
kWh
|
|
04 | 2.2511: Insulate bare equipment | $7,280 | $500 |
$7,280
280,188
kWh
|
|
05 | 2.4133: Use most efficient type of electric motors | $382 | $349 |
$382
10,551
kWh
|
|
TOTAL RECOMMENDED | $77,432 | $72,152 |
$77,432
1,486,811
kWh
|
||
TOTAL IMPLEMENTED | $47,882 | $20,132 |
$47,882
592,321
kWh
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs