Assessment Year | 2002 |
---|---|
Principal Product | Architectural Lighting |
NAICS |
n/a
|
SIC | 3646: Commercial, Industrial, and Institutional Electric Lighting Fixtures |
Sales Range | $10 M to 50M |
# of Employees | 164 |
Plant Area |
90,000
ft2
|
Annual Production | 56,000
pieces
|
Production Hrs. Annual | 4,500
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $119,901 | 4,532,617 |
kWh
|
$0.026 |
Electricity Demand | $98,058 | 11,111 |
kW-mo/yr
|
$8.83 |
Electricity Fees | $31,060 | - |
|
- |
Natural Gas | $43,673 | 9,951 |
MMBtu
|
$4.39 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $81,037 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.448: Install automatic part storage / retreval system | $58,500 | $120,000 | n/a | - | - | - | - | $58,500 |
02 | 3.3122: Use filtration, centrifuging to remove contaminants | $11,400 | $2,000 | n/a | - | - | - |
$14,000
-
Tgal
|
$(-2,600.0) |
03 | 2.7243: Improve air circulation with destratification fans / other methods | $4,750 | $4,800 | n/a |
$(-193.0)
(-6,930)
kWh
|
- |
$4,943
-
MMBtu
|
- | - |
04 | 2.2514: Cover open tanks | $4,508 | $1,512 | n/a | - | - |
$4,508
-
MMBtu
|
- | - |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $931 | $912 | n/a |
$572
20,515
kWh
|
$359
-
kW-mo/yr
|
- | - | - |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $704 | $1,496 | n/a |
$414
14,850
kWh
|
$290
-
kW-mo/yr
|
- | - | - |
07 | 2.7135: Install occupancy sensors | $244 | - | n/a |
$153
5,499
kWh
|
$91
-
kW-mo/yr
|
- | - | - |
TOTAL RECOMMENDED | $81,037 | $130,720 |
$946
33,934
kWh
|
$740
-
kW-mo/yr
|
$9,451
-
MMBtu
|
$14,000
-
Tgal
|
$55,900 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs