ITAC Assessment: UW2407
ITAC logo
ITAC Assessment: UW2407
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2024
Principal Product Guided Missile and Space Vehicle Manufacturing
NAICS 336414: Guided Missile and Space Vehicle Manufacturing
SIC 3761: Guided Missiles and Space Vehicles
Sales Range $100
M
to 500
M
# of Employees 300
Plant Area 152,000
ft2
Annual Production 5,000
pieces
Production Hrs. Annual 8,760
hrs
Location (State) Washington

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $889,456 8,503,400
kWh
Electricity Demand $61,098 11,930
kW-mo/yr
Natural Gas $9,371 702
MMBtu
TOTAL YEARLY COSTS $959,925
RECOMMENDED SAVINGS* $380,089 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Increase in Production Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $69,227 $25,000 $64,874
620,208
kWh
$4,353
-
kW-mo/yr
-
02 2.2622: Replace existing chiller with high efficiency model $90,353 $650,364 $90,353
863,794
kWh
- -
03 2.6218: Turn off equipment when not in use $207,284 $100 $194,255
1,857,120
kWh
$13,029
-
kW-mo/yr
-
04 4.652: Replace existing equipment with more suitable substitutes $7,000 $9,000 - - $7,000
05 2.7135: Install occupancy sensors $2,085 $28,384 $2,085
18,615
kWh
- -
06 2.7243: Improve air circulation with destratification fans / other methods $4,140 $14,800 $4,140
39,579
kWh
- -
TOTAL RECOMMENDED $380,089 $727,648 $355,707
3,399,316
kWh
$17,382
-
kW-mo/yr
$7,000
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Increase in Production Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs