Assessment Year 2009
Principal Product Wine Bottles
NAICS 327213: Glass Container Manufacturing
SIC 3221: Glass Containers
Sales Range $100
M
to 500
M
# of Employees 650
Plant Area 500,000
ft2
Annual Production 500,000,000
units
Production Hrs. Annual 8,760
hrs
Location (State) Washington

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $5,125,118 113,967,235
kWh
Electricity Demand $6,570 13,010
kW-mo/yr
Natural Gas $10,890,883 1,184,770
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $1,833,138 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $30,670

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Consumption Savings
01 2.2442: Preheat combustion air with waste heat $1,467,516 $2,201,270 $303,124
6,811,776
kWh
- $1,164,392
-
MMBtu
-
02 2.2442: Preheat combustion air with waste heat $323,442 $485,164 - - $323,442
-
MMBtu
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $16,942 $76,700 $14,250
320,227
kWh
$2,692
-
kW-mo/yr
- -
04 2.7135: Install occupancy sensors $12,524 $1,960 $12,524
271,441
kWh
- - -
05 2.4133: Use most efficient type of electric motors $10,663 $31,539 $9,303
188,361
kWh
$1,360
-
kW-mo/yr
- -
06 3.4155: Meter waste water $1,060 $12,000 - - - $1,060
-
Tgal
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $847 $560 $834
18,746
kWh
$13
-
kW-mo/yr
- -
08 2.4231: Reduce the pressure of compressed air to the minimum required $144 - $144
2,453
kWh
- - -
TOTAL RECOMMENDED $1,833,138 $2,809,193 $340,179
7,613,004
kWh
$4,065
-
kW-mo/yr
$1,487,834
-
MMBtu
$1,060
-
Tgal
TOTAL IMPLEMENTED $30,670 $90,660 $26,918
594,121
kWh
$2,692
-
kW-mo/yr
- $1,060
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs