| Assessment Year | 2011 |
|---|---|
| Principal Product | Snack Foods |
| NAICS | 311812: Commercial Bakeries |
| SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
| Sales Range | less than $500 k |
| # of Employees | 184 |
| Plant Area |
150,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Michigan |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $218,328 | 4,512,024 |
kWh
|
$0.048 |
| Electricity Demand | $129,997 | 9,041 |
kW-mo/yr
|
$14.38 |
| Natural Gas | $354,225 | 60,903 |
MMBtu
|
$5.82 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $37,367 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $5,696 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2691: Shut off cooling if cold outside air will cool process | $17,794 | $4,850 |
$11,323
234,000
kWh
|
$6,471
-
kW-mo/yr
|
- | - | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,985 | $5,032 |
$3,116
64,392
kWh
|
$1,869
-
kW-mo/yr
|
- | - | |
| 03 | 2.3132: Recharge batteries on during off-peak demand periods | $2,946 | $200 | - |
$1,999
-
kW-mo/yr
|
$947 | - | |
| 04 | 2.7135: Install occupancy sensors | $119 | $600 |
$119
2,457
kWh
|
- | - | - | |
| 05 | 2.6211: Conserve energy by efficient use of vending machines | $82 | $10 |
$82
1,700
kWh
|
- | - | - | |
| 06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $5,186 | $1,200 | - | - | - |
$5,186
-
MMBtu
|
|
| 07 | 2.2437: Recover waste heat from equipment | $2,850 | $1,100 | - | - | - |
$2,850
-
MMBtu
|
|
| 08 | 2.2414: Use waste heat from hot flue gases to preheat | $1,426 | $3,926 | - | - | - |
$1,426
-
MMBtu
|
|
| 09 | 2.2511: Insulate bare equipment | $1,350 | $783 | - | - | - |
$1,350
-
MMBtu
|
|
| 10 | 2.2136: Install / repair insulation on steam lines | $629 | $220 | - | - | - |
$629
-
MMBtu
|
|
| TOTAL RECOMMENDED | $37,367 | $17,921 |
$14,640
302,549
kWh
|
$10,339
-
kW-mo/yr
|
$947 |
$11,441
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $5,696 | $5,262 |
$3,198
66,092
kWh
|
$1,869
-
kW-mo/yr
|
- |
$629
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs