Assessment Year | 2022 |
---|---|
Principal Product | Batteries |
NAICS | 335911: Storage Battery Manufacturing |
SIC | 3691: Storage Batteries |
Sales Range | $100 M to 500M |
# of Employees | 448 |
Plant Area |
252,000
ft2
|
Annual Production | 821,461
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,249,108 | 48,992,000 |
kWh
|
$0.025 |
Electricity Demand | $1,745,632 | 92,266 |
kW-mo/yr
|
$18.92 |
Electricity Fees | $340,819 | - |
|
- |
Natural Gas | $241,443 | 76,683 |
MMBtu
|
$3.15 |
TOTAL YEARLY COSTS | $3,577,002 | |||
RECOMMENDED SAVINGS* | $59,292 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,840 | $16,294 |
$5,449
217,949
kWh
|
$7,391
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $1,208 | $2,171 |
$1,208
48,307
kWh
|
- | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,936 | $19,500 |
$2,936
117,443
kWh
|
- | - | |
04 | 2.9114: Use solar heat to make electricty | $34,406 | $237,031 |
$14,411
576,425
kWh
|
$19,995
-
kW-mo/yr
|
- | |
05 | 2.2414: Use waste heat from hot flue gases to preheat | $7,902 | $63,000 | - | - |
$7,902
-
MMBtu
|
|
TOTAL RECOMMENDED | $59,292 | $337,996 |
$24,004
960,124
kWh
|
$27,386
-
kW-mo/yr
|
$7,902
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs