| Assessment Year | 2022 |
|---|---|
| Principal Product | Metal Tops |
| NAICS | 332119: Metal Crown, Closure, and Other Metal Stamping (except Automotive) |
| SIC | 3466: Crowns and Closures |
| Sales Range | $50 M to 100M |
| # of Employees | 222 |
| Plant Area |
188,000
ft2
|
| Annual Production | 1,900,000,000
pieces
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | Indiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,077,617 | 17,436,480 |
kWh
|
$0.062 |
| Electricity Demand | $322,636 | 28,141 |
kW-mo/yr
|
$11.46 |
| Electricity Fees | $(-39,016.0) | - |
|
- |
| Natural Gas | $1,015,855 | 208,221 |
MMBtu
|
$4.88 |
| TOTAL YEARLY COSTS | $2,377,092 | |||
| RECOMMENDED SAVINGS* | $341,769 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $29,621 | $22,425 |
$23,203
375,446
kWh
|
$6,418
-
kW-mo/yr
|
- | |
| 02 | 2.7135: Install occupancy sensors | $6,795 | $4,853 |
$6,795
109,941
kWh
|
- | - | |
| 03 | 2.7232: Replace existing hvac unit with high efficiency model | $16,260 | $117,000 |
$11,002
177,456
kWh
|
$5,258
-
kW-mo/yr
|
- | |
| 04 | 2.3212: Optimize plant power factor | $38,344 | $59,098 | - |
$38,344
-
kW-mo/yr
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $12,168 | $2,880 |
$12,168
196,264
kWh
|
- | - | |
| 06 | 2.9114: Use solar heat to make electricty | $153,358 | $1,265,937 |
$115,700
1,866,137
kWh
|
$37,658
-
kW-mo/yr
|
- | |
| 07 | 2.4133: Use most efficient type of electric motors | $299 | $1,156 |
$299
4,825
kWh
|
- | - | |
| 08 | 2.2414: Use waste heat from hot flue gases to preheat | $84,924 | $750,000 | - | - |
$84,924
-
MMBtu
|
|
| TOTAL RECOMMENDED | $341,769 | $2,223,349 |
$169,167
2,730,069
kWh
|
$87,678
-
kW-mo/yr
|
$84,924
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs