| Assessment Year | 2019 |
|---|---|
| Principal Product | Bread Products |
| NAICS | 311812: Commercial Bakeries |
| SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
| Sales Range | $10 M to 50M |
| # of Employees | 95 |
| Plant Area |
63,210
ft2
|
| Annual Production | 9,360,000
lb
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $486,602 | 7,480,108 |
kWh
|
$0.065 |
| Electricity Demand | $115,960 | 14,033 |
kW-mo/yr
|
$8.26 |
| Electricity Fees | $390 | - |
|
- |
| Natural Gas | $65,643 | 23,873 |
MMBtu
|
$2.75 |
| TOTAL YEARLY COSTS | $668,595 | |||
| RECOMMENDED SAVINGS* | $53,998 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $48,939 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,268 | $21,268 |
$10,041
154,482
kWh
|
$2,227
-
kW-mo/yr
|
- | - | |
| 02 | 2.4133: Use most efficient type of electric motors | $9,537 | $24,798 |
$7,237
111,344
kWh
|
$2,300
-
kW-mo/yr
|
- | - | |
| 03 | 2.7243: Improve air circulation with destratification fans / other methods | $2,597 | $6,350 |
$2,597
39,953
kWh
|
- | - | - | |
| 04 | 2.2437: Recover waste heat from equipment | $2,462 | $7,500 | - | - |
$2,462
-
MMBtu
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,160 | $456 |
$1,160
17,841
kWh
|
- | - | - | |
| 06 | 2.7135: Install occupancy sensors | $1,039 | $1,393 |
$1,039
15,978
kWh
|
- | - | - | |
| 07 | 4.631: Install an uninteruptable power supply | $24,935 | $1,665 | - | - | - | $24,935 | |
| TOTAL RECOMMENDED | $53,998 | $63,430 |
$22,074
339,598
kWh
|
$4,527
-
kW-mo/yr
|
$2,462
-
MMBtu
|
$24,935 | ||
| TOTAL IMPLEMENTED | $48,939 | $49,580 |
$19,477
299,645
kWh
|
$4,527
-
kW-mo/yr
|
- | $24,935 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs