Assessment Year | 2008 |
---|---|
Principal Product | soft drinks |
NAICS | 312111: Soft Drink Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $10 M to 50M |
# of Employees | 400 |
Plant Area |
430,000
ft2
|
Annual Production | 20,000,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,338,036 | 16,403,519 |
kWh
|
$0.082 |
Electricity Demand | $273,393 | 2,694 |
kW-mo/yr
|
$101.48 |
Electricity Fees | $230,969 | - |
|
- |
Natural Gas | $273,966 | 26,959 |
MMBtu
|
$10.16 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $313,430 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $84,368 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $72,878 | $27,259 |
$72,878
736,145
kWh
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,924 | $9,726 |
$8,924
90,146
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $17,672 | $762 |
$17,672
178,489
kWh
|
- | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $17,409 | - |
$17,409
175,857
kWh
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $156,184 | $102,044 |
$136,840
1,668,751
kWh
|
$19,344
-
kW-mo/yr
|
- | |
06 | 2.7111: Reduce illumination to minimum necessary levels | $7,021 | - |
$7,021
85,616
kWh
|
- | - | |
07 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $20,238 | $21,568 |
$20,238
204,422
kWh
|
- | - | |
08 | 3.4154: Eliminate leaks in water lines and valves | $13,104 | $796 | - | - |
$13,104
-
Tgal
|
|
TOTAL RECOMMENDED | $313,430 | $162,155 |
$280,982
3,139,426
kWh
|
$19,344
-
kW-mo/yr
|
$13,104
-
Tgal
|
||
TOTAL IMPLEMENTED | $84,368 | $32,852 |
$71,264
734,530
kWh
|
- |
$13,104
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs