Assessment Year 2008
Principal Product soft drinks
NAICS 312111: Soft Drink Manufacturing
SIC 2086: Bottled and Canned Soft Drinks and Carbonated Waters
Sales Range $10
M
to 50
M
# of Employees 400
Plant Area 430,000
ft2
Annual Production 20,000,000
pieces
Production Hrs. Annual 8,736
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,338,036 16,403,519
kWh
Electricity Demand $273,393 2,694
kW-mo/yr
Electricity Fees $230,969 -
Natural Gas $273,966 26,959
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $313,430 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $84,368

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Disposal Savings
01 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $72,878 $27,259 $72,878
736,145
kWh
- -
02 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $8,924 $9,726 $8,924
90,146
kWh
- -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $17,672 $762 $17,672
178,489
kWh
- -
04 2.4231: Reduce the pressure of compressed air to the minimum required $17,409 - $17,409
175,857
kWh
- -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $156,184 $102,044 $136,840
1,668,751
kWh
$19,344
-
kW-mo/yr
-
06 2.7111: Reduce illumination to minimum necessary levels $7,021 - $7,021
85,616
kWh
- -
07 2.7121: Utilize daylight whenever possible in lieu of artificial light $20,238 $21,568 $20,238
204,422
kWh
- -
08 3.4154: Eliminate leaks in water lines and valves $13,104 $796 - - $13,104
-
Tgal
TOTAL RECOMMENDED $313,430 $162,155 $280,982
3,139,426
kWh
$19,344
-
kW-mo/yr
$13,104
-
Tgal
TOTAL IMPLEMENTED $84,368 $32,852 $71,264
734,530
kWh
- $13,104
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Disposal Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs