Assessment Year | 2002 |
---|---|
Principal Product | Non Woven Fabrics |
NAICS |
n/a
|
SIC | 2297: Non-woven Fabrics |
Sales Range | n/a |
# of Employees | 105 |
Plant Area |
25,000
ft2
|
Annual Production | 10,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $611,554 | 26,846,040 |
kWh
|
$0.023 |
Electricity Demand | $430,794 | 47,422 |
kW-mo/yr
|
$9.08 |
Other Energy | $374,559 | 54,896 |
MMBtu
|
$6.82 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $343,707 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $44,938 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,492 | $10,725 |
$1,327
57,678
kWh
|
$1,165
-
kW-mo/yr
|
- | - | |
02 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $23,630 | - |
$20,215
518,343
kWh
|
- | $419 | $2,996 | |
03 | 2.4133: Use most efficient type of electric motors | $29,432 | $110,539 |
$19,103
830,556
kWh
|
$10,329
-
kW-mo/yr
|
- | - | |
04 | 2.4321: Upgrade obsolete equipment | $265,075 | $1,028,304 |
$265,075
6,796,798
kWh
|
- | - | - | |
05 | 2.4238: Do not use compressed air for personal cooling | $7,014 | - |
$7,014
179,839
kWh
|
- | - | - | |
06 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $3,158 | $1,895 | - | - | $3,158 | - | |
07 | 4.632: Change operating conditions | $6,000 | $472 | - | - | $6,000 | - | |
08 | 4.513: Re-arrange equipment layout to reduce labor costs | $6,906 | $600 | - | - | $6,906 | - | |
TOTAL RECOMMENDED | $343,707 | $1,152,535 |
$312,734
8,383,214
kWh
|
$11,494
-
kW-mo/yr
|
$16,483 | $2,996 | ||
TOTAL IMPLEMENTED | $44,938 | $121,736 |
$27,444
1,068,073
kWh
|
$11,494
-
kW-mo/yr
|
$6,000 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs