Assessment Year | 1997 |
---|---|
Principal Product | Paper & plastic bags & polyethylene sheeting |
NAICS |
n/a
|
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $1 M to 5M |
# of Employees | 118 |
Plant Area |
186,000
ft2
|
Annual Production | 188,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $154,473 | 3,716,589 |
kWh
|
$0.042 |
Electricity Demand | $52,927 | 7,396 |
kW-mo/yr
|
$7.16 |
Natural Gas | $21,124 | 2,995 |
MMBtu
|
$7.05 |
LPG | $13,508 | 1,765 |
MMBtu
|
$7.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $74,750 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,489 | $8,739 |
$3,260
77,667
kWh
|
$1,229
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,714 | $5,256 |
$3,563
84,701
kWh
|
$1,151
-
kW-mo/yr
|
- | - | - | |
03 | 2.7122: Disconnect ballasts | $2,703 | $480 |
$1,993
46,893
kWh
|
$710
-
kW-mo/yr
|
- | - | - | |
04 | 2.7145: Install skylights | $4,814 | $8,200 |
$4,814
114,596
kWh
|
- | - | - | - | |
05 | 2.4133: Use most efficient type of electric motors | $1,260 | $1,459 |
$1,019
24,326
kWh
|
$241
-
kW-mo/yr
|
- | - | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,732 | $1,200 |
$2,732
48,652
kWh
|
- | - | - | - | |
07 | 4.521: Clear and rent existing space | $48,686 | $960 | - | - | - | $48,686 | - | |
08 | 3.1191: Change procedures / equipment / operating conditions | $672 | $600 | - | - |
$672
-
lb
|
- | - | |
09 | 3.1121: Use more efficient adhesive applicators | $4,680 | $320 | - | - | - | - | $4,680 | |
TOTAL RECOMMENDED | $74,750 | $27,214 |
$17,381
396,835
kWh
|
$3,331
-
kW-mo/yr
|
$672
-
lb
|
$48,686 | $4,680 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs