Assessment Year | 1996 |
---|---|
Principal Product | Animal Feed |
NAICS |
n/a
|
SIC | 2048: Prepared Feed and Feed Ingredients for Animals and Fowls, Except Dogs and Cats |
Sales Range | $10 M to 50M |
# of Employees | 28 |
Plant Area |
40,000
ft2
|
Annual Production | 105,288
ton
|
Production Hrs. Annual | 5,616
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $92,011 | 2,041,325 |
kWh
|
$0.045 |
Electricity Demand | $66,967 | 6,964 |
kW-mo/yr
|
$9.62 |
Natural Gas | $2,328 | 358 |
MMBtu
|
$6.50 |
Fuel Oil #2 | $29,943 | 6,450 |
MMBtu
|
$4.64 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $66,107 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $1,837 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings | Personnel Changes Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,854 | $13,343 |
$2,710
60,375
kWh
|
$144
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $364 | $5,028 |
$251
5,569
kWh
|
$113
-
kW-mo/yr
|
- | - | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $981 | $2,530 |
$981
20,223
kWh
|
- | - | - | - | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,837 | $1,350 |
$1,837
23,447
kWh
|
- | - | - | - | - | |
05 | 2.2425: Use flue gases to heat process or service water | $1,164 | $3,500 | - | - |
$1,164
-
MMBtu
|
- | - | - | |
06 | 2.2121: Increase amount of condensate returned | $5,675 | $5,000 | - | - | - |
$2,488
-
MMBtu
|
- |
$3,187
-
Tgal
|
|
07 | 3.2176: Increase use of automation | $53,232 | $133,000 |
$(-109.0)
(-2,345)
kWh
|
$(-12.0)
-
kW-mo/yr
|
- | - | $53,353 | - | |
TOTAL RECOMMENDED | $66,107 | $163,751 |
$5,670
107,269
kWh
|
$245
-
kW-mo/yr
|
$1,164
-
MMBtu
|
$2,488
-
MMBtu
|
$53,353 |
$3,187
-
Tgal
|
||
TOTAL IMPLEMENTED | $1,837 | $1,350 |
$1,837
23,447
kWh
|
- | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #2 Savings | Personnel Changes Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs