Assessment Year | 1994 |
---|---|
Principal Product | commercial printing |
NAICS |
n/a
|
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 240 |
Plant Area |
150,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Kentucky |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $107,745 | 1,941,383 |
kWh
|
$0.055 |
Natural Gas | $25,962 | 5,142 |
MMBtu
|
$5.05 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $42,064 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,409 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $11,729 | $21,000 |
$11,729
-
kWh
|
- | |
02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $18,122 | - |
$18,122
-
kWh
|
- | |
03 | 2.2437: Recover waste heat from equipment | $4,381 | $7,000 |
$3,241
38,980
kWh
|
$1,140
-
MMBtu
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,299 | $15,139 |
$7,299
126,026
kWh
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $533 | $518 |
$533
8,206
kWh
|
- | |
TOTAL RECOMMENDED | $42,064 | $43,657 |
$40,924
173,212
kWh
|
$1,140
-
MMBtu
|
||
TOTAL IMPLEMENTED | $23,409 | $43,139 |
$22,269
165,006
kWh
|
$1,140
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs