Assessment Year | 2022 |
---|---|
Principal Product | Water Meter |
NAICS | 334514: Totalizing Fluid Meter and Counting Device Manufacturing |
SIC | 3824: Totalizing Fluid Meters and Counting Devices |
Sales Range | $100 M to 500M |
# of Employees | 495 |
Plant Area |
251,200
ft2
|
Annual Production | 2,200,000
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,428,851 | 24,838,630 |
kWh
|
$0.058 |
Electricity Demand | $218,006 | 50,555 |
kW-mo/yr
|
$4.31 |
Electricity Fees | $7,730 | - |
|
- |
Natural Gas | $94,665 | 14,939 |
MMBtu
|
$6.34 |
TOTAL YEARLY COSTS | $1,749,252 | |||
RECOMMENDED SAVINGS* | $26,299 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,455 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,600 | $9,695 |
$10,056
174,790
kWh
|
$1,490
-
kW-mo/yr
|
$54 | |
02 | 2.7221: Lower temperature during the winter season and vice-versa | $12,152 | $150 |
$12,095
210,242
kWh
|
- | $57 | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,692 | $373 |
$1,418
24,656
kWh
|
$266
-
kW-mo/yr
|
$8 | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $855 | $1,067 |
$739
12,838
kWh
|
$112
-
kW-mo/yr
|
$4 | |
TOTAL RECOMMENDED | $26,299 | $11,285 |
$24,308
422,526
kWh
|
$1,868
-
kW-mo/yr
|
$123 | ||
TOTAL IMPLEMENTED | $12,455 | $10,762 |
$10,795
187,628
kWh
|
$1,602
-
kW-mo/yr
|
$58 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs