| Assessment Year | 2021 |
|---|---|
| Principal Product | Head Lamps, Tail Lamps, Shifters |
| NAICS | 336320: Motor Vehicle Electrical and Electronic Equipment Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $100 M to 500M |
| # of Employees | 800 |
| Plant Area |
750,000
ft2
|
| Annual Production | 1,820,000
pieces
|
| Production Hrs. Annual | 2,880
hrs
|
| Location (State) | Tennessee |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $2,003,490 | 25,721,956 |
kWh
|
$0.078 | |
| Electricity Demand | $784,635 | 125,468 |
kW-mo/yr
|
$6.25 | |
| Natural Gas | $106,759 | 11,549 |
MMBtu
|
$9.24 | |
| Waste Disposal Costs | |||||
| Water Usage | $29,707 | 4,331 |
Tgal
|
$6.86 | |
| TOTAL YEARLY COSTS | $2,924,591 | ||||
| RECOMMENDED SAVINGS* | $186,830 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | $98,296 | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $87,163 | $208,768 |
$73,063
938,036
kWh
|
$14,100
-
kW-mo/yr
|
- | |
| 02 | 2.9113: Use solar heat for heat | $66,558 | $342,530 |
$66,558
854,507
kWh
|
- | - | |
| 03 | 2.3212: Optimize plant power factor | $17,343 | $140,000 | - | - | $17,343 | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,133 | $1,500 |
$8,652
111,082
kWh
|
$2,481
-
kW-mo/yr
|
- | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,071 | $325 |
$2,071
25,892
kWh
|
- | - | |
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,717 | $5,000 |
$1,717
22,045
kWh
|
- | - | |
| 07 | 3.4151: Minimize water usage | $846 | $1,753 |
$(-25.0)
(-321)
kWh
|
$(-13.1)
-
kW-mo/yr
|
$884 | |
| TOTAL RECOMMENDED | $186,830 | $699,876 |
$152,036
1,951,241
kWh
|
$16,568
-
kW-mo/yr
|
$18,227 | ||
| TOTAL IMPLEMENTED | $98,296 | $210,268 |
$81,715
1,049,118
kWh
|
$16,581
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs