Assessment Year | 2020 |
---|---|
Principal Product | Aluminum tubing |
NAICS | 331318: Other Aluminum Rolling, Drawing, and Extruding |
SIC | 3354: Aluminum Extruded Products |
Sales Range | $10 M to 50M |
# of Employees | 39 |
Plant Area |
57,200
ft2
|
Annual Production | 11,124,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Texas |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $166,494 | 3,298,320 |
kWh
|
$0.050 | |
Electricity Demand | $100,061 | 10,008 |
kW-mo/yr
|
$10.00 | |
Electricity Fees | $2,383 | - |
|
- | |
Natural Gas | $117,144 | 18,525 |
MMBtu
|
$6.32 | |
Waste Disposal Costs | |||||
Water Usage | $4,119 | 1,987 |
Tgal
|
$2.07 | |
Water Disposal | $7,801 | 1,987 |
Tgal
|
$3.93 | |
TOTAL YEARLY COSTS | $398,002 | ||||
RECOMMENDED SAVINGS* | $30,212 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $30,212 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,791 | $1,500 |
$10,037
195,268
kWh
|
$3,754
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,401 | $9,785 |
$6,842
133,119
kWh
|
$2,559
-
kW-mo/yr
|
- | |
03 | 3.4155: Meter waste water | $7,020 | $1,511 | - | - |
$7,020
-
Tgal
|
|
TOTAL RECOMMENDED | $30,212 | $12,796 |
$16,879
328,387
kWh
|
$6,314
-
kW-mo/yr
|
$7,020
-
Tgal
|
||
TOTAL IMPLEMENTED | $30,212 | $12,796 |
$16,879
328,387
kWh
|
$6,314
-
kW-mo/yr
|
$7,020
-
Tgal
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs