Assessment Year | 2013 |
---|---|
Principal Product | Paper Cups and Plastic Lids |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
452,000
ft2
|
Annual Production | 60,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,355,870 | 19,406,067 |
kWh
|
$0.070 |
Electricity Demand | $430,421 | 34,729 |
kW-mo/yr
|
$12.39 |
Electricity Fees | $10,353 | - |
|
- |
Natural Gas | $114,492 | 16,176 |
MMBtu
|
$7.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $194,257 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $123,597 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,213 | - |
$7,213
103,228
kWh
|
- | - | - | |
02 | 2.2511: Insulate bare equipment | $3,654 | $436 |
$2,713
38,824
kWh
|
$941
-
kW-mo/yr
|
- | - | |
03 | 2.4322: Use or replace with energy efficient substitutes | $34,286 | $4,843 |
$25,935
371,194
kWh
|
$8,351
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $620 | $359 |
$455
6,517
kWh
|
$165
-
kW-mo/yr
|
- | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $52,879 | $35,000 |
$46,613
667,135
kWh
|
$6,266
-
kW-mo/yr
|
- | - | |
06 | 2.4239: Eliminate or reduce compressed air usage | $15,908 | $12,499 |
$12,799
183,189
kWh
|
$3,109
-
kW-mo/yr
|
- | - | |
07 | 2.7144: Install spectral reflectors / delamp | $3,902 | $3,286 |
$2,626
37,580
kWh
|
$1,276
-
kW-mo/yr
|
- | - | |
08 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $9,037 | $10,104 |
$7,271
104,069
kWh
|
$1,766
-
kW-mo/yr
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,058 | $18,484 |
$10,058
143,951
kWh
|
- | - | - | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,646 | $8,690 |
$2,129
30,466
kWh
|
$517
-
kW-mo/yr
|
- | - | |
11 | 2.7135: Install occupancy sensors | $6,030 | $22,132 |
$4,852
69,446
kWh
|
$1,178
-
kW-mo/yr
|
- | - | |
12 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $24,184 | $91,986 |
$19,457
278,481
kWh
|
$4,727
-
kW-mo/yr
|
- | - | |
13 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,151 | $18,136 |
$3,415
48,882
kWh
|
$551
-
kW-mo/yr
|
$222 | $(-37.0) | |
14 | 2.6218: Turn off equipment when not in use | $370 | $1,980 |
$370
5,301
kWh
|
- | - | - | |
15 | 2.2628: Utilize a less expensive cooling method | $19,319 | $118,398 |
$15,815
226,343
kWh
|
$3,504
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $194,257 | $346,333 |
$161,721
2,314,606
kWh
|
$32,351
-
kW-mo/yr
|
$222 | $(-37.0) | ||
TOTAL IMPLEMENTED | $123,597 | $63,241 |
$102,999
1,474,156
kWh
|
$20,598
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs