Assessment Year | 2007 |
---|---|
Principal Product | frozen bakery products |
NAICS | 311813: Frozen Cakes, Pies, and Other Pastries Manufacturing |
SIC | 2053: Frozen Bakery Products, Except Bread |
Sales Range | $100 M to 500M |
# of Employees | 680 |
Plant Area |
460,000
ft2
|
Annual Production | 7,800,000
units
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,225,481 | 26,719,284 |
kWh
|
$0.083 |
Electricity Demand | $222,204 | 49,579 |
kW-mo/yr
|
$4.48 |
Electricity Fees | $15,036 | - |
|
- |
Natural Gas | $592,428 | 85,662 |
MMBtu
|
$6.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $576,424 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,599 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2621: Modify refrigeration system to operate at a lower pressure | $250,944 | $80,000 |
$250,944
3,027,007
kWh
|
- | - | |
02 | 2.2626: Avoid frost formation on evaporators | $86,147 | $41,628 |
$86,147
1,039,049
kWh
|
- | - | |
03 | 2.2621: Modify refrigeration system to operate at a lower pressure | $8,746 | $7,500 |
$7,949
95,875
kWh
|
$797
-
kW-mo/yr
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,598 | $1,412 |
$1,465
18,113
kWh
|
$133
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $33,282 | $34,413 |
$33,282
401,423
kWh
|
- | - | |
06 | 2.7135: Install occupancy sensors | $17,040 | $25,438 |
$15,593
188,069
kWh
|
$1,447
-
kW-mo/yr
|
- | |
07 | 2.4131: Size electric motors for peak operating efficiency | $14,176 | $22,780 |
$12,926
155,919
kWh
|
$1,250
-
kW-mo/yr
|
- | |
08 | 2.2621: Modify refrigeration system to operate at a lower pressure | $130,413 | $250,000 |
$116,704
1,407,600
kWh
|
$13,709
-
kW-mo/yr
|
- | |
09 | 2.2414: Use waste heat from hot flue gases to preheat | $6,865 | $13,500 | - | - |
$6,865
-
MMBtu
|
|
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $25,677 | $54,912 |
$23,631
285,023
kWh
|
$2,046
-
kW-mo/yr
|
- | |
11 | 2.1241: Reduce excessive boiler blowdown | $1,536 | $5,000 | - | - |
$1,536
-
MMBtu
|
|
TOTAL RECOMMENDED | $576,424 | $536,583 |
$548,641
6,618,078
kWh
|
$19,382
-
kW-mo/yr
|
$8,401
-
MMBtu
|
||
TOTAL IMPLEMENTED | $48,599 | $85,192 |
$44,506
536,817
kWh
|
$4,093
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs