| Assessment Year | 1998 |
|---|---|
| Principal Product | Canned Fruits |
| NAICS |
n/a
|
| SIC | 2030: |
| Sales Range | $50 M to 100M |
| # of Employees | 1,500 |
| Plant Area |
500,000
ft2
|
| Annual Production | 500,000,000
lb
|
| Production Hrs. Annual | 1,584
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $376,035 | 10,390,973 |
kWh
|
$0.036 |
| Electricity Demand | $165,873 | 21,526 |
kW-mo/yr
|
$7.71 |
| Natural Gas | $463,141 | 214,036 |
MMBtu
|
$2.16 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $224,635 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Water Consumption Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,127 | $50 |
$992
27,550
kWh
|
$135
-
kW-mo/yr
|
- | - | - | - | |
| 02 | 2.2135: Repair and eliminate steam leaks | $1,107 | $1,250 | - | - |
$1,107
-
MMBtu
|
- | - | - | |
| 03 | 2.4133: Use most efficient type of electric motors | $2,947 | $7,021 |
$2,316
63,892
kWh
|
$631
-
kW-mo/yr
|
- | - | - | - | |
| 04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,191 | $5,404 |
$1,722
47,479
kWh
|
$469
-
kW-mo/yr
|
- | - | - | - | |
| 05 | 3.5313: Increase amount of waste recovered for resale | $42,254 | - | - | - | - | - |
$42,254
-
lb
|
- | |
| 06 | 2.2121: Increase amount of condensate returned | $21,972 | $2,000 |
$6,949
942,849
kWh
|
- | - |
$11,890
-
Tgal
|
- |
$3,133
-
Tgal
|
|
| 07 | 3.4111: Use closed cycle process to minimize waste water production | $7,108 | $399 |
$(-20.0)
(-293)
kWh
|
- | - |
$4,762
-
Tgal
|
- |
$2,366
-
Tgal
|
|
| 08 | 3.4111: Use closed cycle process to minimize waste water production | $1,183 | $399 |
$(-20.0)
(-293)
kWh
|
- | - |
$952
-
Tgal
|
- |
$251
-
Tgal
|
|
| 09 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $144,746 | $120,400 | - | - | - | - |
$144,746
-
lb
|
- | |
| TOTAL RECOMMENDED | $224,635 | $136,923 |
$11,939
1,081,184
kWh
|
$1,235
-
kW-mo/yr
|
$1,107
-
MMBtu
|
$17,604
-
Tgal
|
$187,000
-
lb
|
$5,750
-
Tgal
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Water Consumption Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs