Assessment Year | 1994 |
---|---|
Principal Product | Fiberglass Building Insulation Material |
NAICS |
n/a
|
SIC | 3296: Mineral Wool |
Sales Range | $50 M to 100M |
# of Employees | 366 |
Plant Area |
606,900
ft2
|
Annual Production | 70,000
ton
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $5,294,130 | 105,765,242 |
kWh
|
$0.050 |
Natural Gas | $549,507 | 177,578 |
MMBtu
|
$3.09 |
LPG | $19,757 | 1,918 |
MMBtu
|
$10.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $979,577 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $88,823 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $24,584 | $57,981 |
$24,584
-
kWh
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $39,338 | $33,934 |
$39,338
777,550
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,487 | $6,576 |
$3,487
68,875
kWh
|
- | |
04 | 2.7135: Install occupancy sensors | $5,124 | $854 |
$5,124
101,407
kWh
|
- | |
05 | 2.2414: Use waste heat from hot flue gases to preheat | $35,685 | $100,000 | - |
$35,685
-
MMBtu
|
|
06 | 2.4239: Eliminate or reduce compressed air usage | $16,290 | - |
$16,290
322,098
kWh
|
- | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $55,136 | $55,428 |
$55,136
1,089,683
kWh
|
- | |
08 | 2.4239: Eliminate or reduce compressed air usage | $6,496 | - |
$6,496
127,784
kWh
|
- | |
09 | 2.4322: Use or replace with energy efficient substitutes | $793,437 | $1,350,000 |
$1,084,346
21,429,660
kWh
|
$(-290,909.0)
-
MMBtu
|
|
TOTAL RECOMMENDED | $979,577 | $1,604,773 |
$1,234,801
23,917,057
kWh
|
$(-255,224.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $88,823 | $99,345 |
$88,823
1,269,930
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs