Assessment Year | 2019 |
---|---|
Principal Product | Circuit Boards |
NAICS | 334111: Electronic Computer Manufacturing |
SIC | 3571: Electronic Computers |
Sales Range | $10 M to 50M |
# of Employees | 124 |
Plant Area |
83,972
ft2
|
Annual Production | 10,000
units
|
Production Hrs. Annual | 2,860
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $108,482 | 908,236 |
kWh
|
$0.12 |
Electricity Demand | $65,983 | 4,054 |
kW-mo/yr
|
$16.28 |
Electricity Fees | $25,648 | - |
|
- |
Natural Gas | $5,220 | 689 |
MMBtu
|
$7.57 |
Other Gas | $721 | 1 |
MMBtu
|
$721.00 |
TOTAL YEARLY COSTS | $206,054 | |||
RECOMMENDED SAVINGS* | $17,430 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,430 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,633 | $32,287 |
$7,273
60,928
kWh
|
$6,044
-
kW-mo/yr
|
- | $316 | |
02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $2,578 | $7,495 |
$2,766
23,166
kWh
|
$667
-
kW-mo/yr
|
$(-855.0)
-
MMBtu
|
- | |
03 | 2.7135: Install occupancy sensors | $812 | $1,395 |
$812
6,804
kWh
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $407 | - |
$407
3,415
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $17,430 | $41,177 |
$11,258
94,313
kWh
|
$6,711
-
kW-mo/yr
|
$(-855.0)
-
MMBtu
|
$316 | ||
TOTAL IMPLEMENTED | $17,430 | $41,177 |
$11,258
94,313
kWh
|
$6,711
-
kW-mo/yr
|
$(-855.0)
-
MMBtu
|
$316 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs