| Assessment Year | 1995 |
|---|---|
| Principal Product | Cncrete and Steel Pipes |
| NAICS |
n/a
|
| SIC | 3275: Gypsum Products |
| Sales Range | $10 M to 50M |
| # of Employees | 200 |
| Plant Area |
116,000
ft2
|
| Annual Production | 18,000,000
lb
|
| Production Hrs. Annual | 4,250
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $344,782 | 3,736,225 |
kWh
|
$0.092 |
| Natural Gas | $138,724 | 52,081 |
MMBtu
|
$2.66 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $52,263 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $46,080 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $16,656 | $15,430 |
$16,656
180,539
kWh
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $16,434 | $1,200 |
$16,434
177,608
kWh
|
- | |
| 03 | 2.2135: Repair and eliminate steam leaks | $3,100 | $2,475 | - |
$3,100
-
MMBtu
|
|
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,259 | $6,568 |
$6,259
68,288
kWh
|
- | |
| 05 | 2.7144: Install spectral reflectors / delamp | $3,631 | $4,780 |
$3,631
36,928
kWh
|
- | |
| 06 | 2.7134: Use photocell controls | $6,183 | $1,150 |
$6,183
63,892
kWh
|
- | |
| TOTAL RECOMMENDED | $52,263 | $31,603 |
$49,163
527,255
kWh
|
$3,100
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $46,080 | $30,453 |
$42,980
463,363
kWh
|
$3,100
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs