| Assessment Year | 2026 |
|---|---|
| Principal Product | education |
| NAICS | 611310: Colleges, Universities, and Professional Schools |
| SIC | 8221: Colleges, Universities, and Professional Schools |
| Sales Range | less than $500 k |
| # of Employees | 1 |
| Plant Area |
138,762
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 3,120
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | ||
|---|---|---|---|---|---|
| Electricity Usage | $115,086 | 2,253,000 |
kWh
|
$0.051 | |
| Electricity Demand | $92,753 | 5,427 |
kW-mo/yr
|
$17.09 | |
| Electricity Fees | $49,681 | - |
|
- | |
| Natural Gas | $4,260 | 374 |
MMBtu
|
$11.38 | |
| Waste Disposal Costs | |||||
| Water Usage | $1 | 1 |
Tgal
|
$1.00 | |
| TOTAL YEARLY COSTS | $261,781 | ||||
| RECOMMENDED SAVINGS* | $28,184 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
| IMPLEMENTED SAVINGS* | - | ||||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $12,770 | $36,078 |
$6,923
135,519
kWh
|
$5,591
-
kW-mo/yr
|
$256
-
MMBtu
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,320 | $59,060 |
$5,771
112,978
kWh
|
$5,549
-
kW-mo/yr
|
- | |
| 03 | 2.7423: Reduce heat gain by window tinting | $1,110 | $2,717 |
$1,110
21,733
kWh
|
- | - | |
| 04 | 2.7111: Reduce illumination to minimum necessary levels | $1,828 | - |
$1,828
35,793
kWh
|
- | - | |
| 05 | 2.7314: Reduce ventilation air | $1,156 | $325 |
$803
15,725
kWh
|
- |
$353
-
MMBtu
|
|
| TOTAL RECOMMENDED | $28,184 | $98,180 |
$16,435
321,748
kWh
|
$11,140
-
kW-mo/yr
|
$609
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs