| Assessment Year | 2024 |
|---|---|
| Principal Product | Education |
| NAICS | 611210: Junior Colleges |
| SIC | 8222: Junior Colleges and Technical Institutes |
| Sales Range | less than $500 k |
| # of Employees | 30 |
| Plant Area |
100,000
ft2
|
| Annual Production | 100
pieces
|
| Production Hrs. Annual | 3,380
hrs
|
| Location (State) | Oregon |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $13,812 | 230,200 |
kWh
|
$0.060 |
| Electricity Demand | $302 | 45 |
kW-mo/yr
|
$6.70 |
| Natural Gas | $47,833 | 7,359 |
MMBtu
|
$6.50 |
| TOTAL YEARLY COSTS | $61,947 | |||
| RECOMMENDED SAVINGS* | $42,996 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,643 | $49,125 |
$5,463
91,044
kWh
|
$180
-
kW-mo/yr
|
- | |
| 02 | 2.7135: Install occupancy sensors | $559 | $1,200 |
$559
9,318
kWh
|
- | - | |
| 03 | 2.7224: Reduce space conditioning during non-working hours | $9,215 | $1,500 |
$407
6,790
kWh
|
- |
$8,808
-
MMBtu
|
|
| 04 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $27,579 | $200,000 |
$539
8,990
kWh
|
- |
$27,040
-
MMBtu
|
|
| TOTAL RECOMMENDED | $42,996 | $251,825 |
$6,968
116,142
kWh
|
$180
-
kW-mo/yr
|
$35,848
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs