Assessment Year | 2024 |
---|---|
Principal Product | Education |
NAICS | 611210: Junior Colleges |
SIC | 8222: Junior Colleges and Technical Institutes |
Sales Range | less than $500 k |
# of Employees | 30 |
Plant Area |
100,000
ft2
|
Annual Production | 100
pieces
|
Production Hrs. Annual | 3,380
hrs
|
Location (State) | Oregon |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $13,812 | 230,200 |
kWh
|
$0.060 |
Electricity Demand | $302 | 45 |
kW-mo/yr
|
$6.70 |
Natural Gas | $47,833 | 7,359 |
MMBtu
|
$6.50 |
TOTAL YEARLY COSTS | $61,947 | |||
RECOMMENDED SAVINGS* | $42,996 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,643 | $49,125 |
$5,463
91,044
kWh
|
$180
-
kW-mo/yr
|
- | |
02 | 2.7135: Install occupancy sensors | $559 | $1,200 |
$559
9,318
kWh
|
- | - | |
03 | 2.7224: Reduce space conditioning during non-working hours | $9,215 | $1,500 |
$407
6,790
kWh
|
- |
$8,808
-
MMBtu
|
|
04 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $27,579 | $200,000 |
$539
8,990
kWh
|
- |
$27,040
-
MMBtu
|
|
TOTAL RECOMMENDED | $42,996 | $251,825 |
$6,968
116,142
kWh
|
$180
-
kW-mo/yr
|
$35,848
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs