Assessment Year 2016
Principal Product Furniture
NAICS 337121: Upholstered Household Furniture Manufacturing
SIC 2512: Wood Household Furniture, Upholstered
Sales Range $100
M
to 500
M
# of Employees 350
Plant Area 475,000
ft2
Annual Production 350,000
units
Production Hrs. Annual 2,923
hrs
Location (State) Arkansas

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $162,813 2,987,400
kWh
Electricity Demand $113,521 11,606
kW-mo/yr
Natural Gas $35,462 4,358
MMBtu
TOTAL YEARLY COSTS $311,796
RECOMMENDED SAVINGS* $30,742 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $2,222

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7135: Install occupancy sensors $914 $1,425 $914
16,771
kWh
-
02 2.7135: Install occupancy sensors $366 $835 $366
6,708
kWh
-
03 2.7142: Utilize higher efficiency lamps and/or ballasts $16,324 $18,000 $9,399
172,457
kWh
$6,925
-
kW-mo/yr
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,222 $1,107 $2,222
40,776
kWh
-
05 2.3131: Reschedule plant operations or reduce load to avoid peaks $10,916 - - $10,916
-
kW-mo/yr
TOTAL RECOMMENDED $30,742 $21,367 $12,901
236,712
kWh
$17,841
-
kW-mo/yr
TOTAL IMPLEMENTED $2,222 $1,107 $2,222
40,776
kWh
-
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs