Assessment Year | 2005 |
---|---|
Principal Product | Plastic Sheeting |
NAICS | 326160: Plastics Bottle Manufacturing |
SIC | 3085: Plastics Bottles |
Sales Range | $50 M to 100M |
# of Employees | 70 |
Plant Area |
48,000
ft2
|
Annual Production | 52,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Oklahoma |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $209,750 | 12,844,000 |
kWh
|
$0.016 |
Electricity Demand | $208,640 | 20,561 |
kW-mo/yr
|
$10.15 |
Electricity Fees | $(-14,796.0) | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $55,294 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $19,953 | $32,150 |
$19,953
612,064
kWh
|
- | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $978 | $6,015 |
$978
30,000
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,199 | $1,007 |
$4,533
278,100
kWh
|
$3,866
-
kW-mo/yr
|
$(-200.0) | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,908 | $4,618 |
$2,109
129,392
kWh
|
$1,799
-
kW-mo/yr
|
- | |
05 | 2.2437: Recover waste heat from equipment | $16,153 | $14,047 |
$8,718
534,877
kWh
|
$7,435
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $199 | $302 |
$21
1,282
kWh
|
$18
-
kW-mo/yr
|
$160 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $842 | $6,783 |
$418
25,643
kWh
|
$424
-
kW-mo/yr
|
- | |
08 | 2.4133: Use most efficient type of electric motors | $5,062 | $50,389 |
$945
57,975
kWh
|
- | $4,117 | |
TOTAL RECOMMENDED | $55,294 | $115,311 |
$37,675
1,669,333
kWh
|
$13,542
-
kW-mo/yr
|
$4,077 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs