Assessment Year | 2025 |
---|---|
Principal Product | Battery Chargers |
NAICS | 335999: All Other Miscellaneous Electrical Equipment and Component Manufacturing |
SIC | 3629: Electrical Industrial Apparatus, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 100 |
Plant Area |
83,050
ft2
|
Annual Production | 200,000
units
|
Production Hrs. Annual | 4,250
hrs
|
Location (State) | Nebraska |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $36,406 | 1,438,943 |
kWh
|
$0.025 | |
Electricity Demand | $106,544 | 4,898 |
kW-mo/yr
|
$21.75 | |
Electricity Fees | $11,314 | - |
|
- | |
Natural Gas | $33,740 | 5,541 |
MMBtu
|
$6.09 | |
Waste Disposal Costs | |||||
Water Usage | $2,601 | 952 |
Tgal
|
$2.73 | |
Water Disposal | $3,171 | 952 |
Tgal
|
$3.33 | |
Other Liquid (non-haz) | $3,340 | 1 |
gal
|
$3,340.00 | |
TOTAL YEARLY COSTS | $197,116 | ||||
RECOMMENDED SAVINGS* | $34,459 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,339 | $29,931 |
$5,507
211,914
kWh
|
$13,597
-
kW-mo/yr
|
- | $1,235 | - | |
02 | 2.3312: Install efficient rectifiers | $9,857 | $75,000 |
$1,011
38,880
kWh
|
$8,846
-
kW-mo/yr
|
- | - | - | |
03 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,457 | $104 | - |
$2,457
-
kW-mo/yr
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $771 | $26 |
$279
10,747
kWh
|
$492
-
kW-mo/yr
|
- | - | - | |
05 | 3.4155: Meter waste water | $564 | $1,582 | - | - |
$564
-
Tgal
|
- | - | |
06 | 2.8121: Apply for tax-free status for energy purchases | $471 | $416 | - | - | - | - | $471 | |
TOTAL RECOMMENDED | $34,459 | $107,059 |
$6,797
261,541
kWh
|
$25,392
-
kW-mo/yr
|
$564
-
Tgal
|
$1,235 | $471 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs